Title

Secure Power Distribution against Reactive Power Control Malfunction in der Units

Document Type

Article

Publication Date

6-1-2021

Abstract

Penetration of distributed energy resources (DERs) such as wind, solar and battery units are rapidly increasing in distribution power system (DPS). In view of power grid reliability and efficiency, cyber and physical secure of these units are highly important since it can directly impact power system operations. This paper investigates the dynamic behavior of power distribution during cyber, physical and natural strikes on reactive power control in DER units. Various fault scenarios including modifications in voltage-reactive power (Volt-Var) curve pattern such as slope of the curve, dead band; and changes in capacitive or/and inductive reactive power delivery to the power grid are presented. Further, fault scenarios are investigated with the presence of dynamic VAR (volt-ampere reactive) compensation (DVC) units in the system. A southern California 140-bus commercial distribution power system is selected as a test system and faults are analyzed in both Matlab/Simulink and ETAP simulation platforms. The results evidence that the modifications in reactive power control values at DER units significantly affects the voltage quality/security of the system and affect the number of switching actions of voltage regulators (VRs). In contrast, DPS connected with DVCs improves voltage quality and reduces the number of switching actions of VRs, also voltage quality/security is maintained during the faults.

Publication Source (Journal or Book title)

IEEE Transactions on Power Delivery

First Page

1552

Last Page

1561